| |
To use the feature of security system, the required
sensors are to be connected to the system and
should be defined as given by this programming.
The sensors for Intruder & Fire security system
comes in either Normally Open (NO) or Normally
Closed (NC) mode, which means for NO sensors in
case of break, sensors will have a closed contact
and for NC sensors in case of break, sensors will
have an open contact. Multiple NO sensors can
be connected in parallel for a particular Zone
and similarly, Multiple NC sensors can be connected
in series for a particular Zone, to detect a break.
The Zones in security can be dedicated for Area
or Sensor Type or both together, but for a particular
zone, NO & NC both sensors can not be connected.
Certain sensors like Smoke Detectors, Glass Break
Detectors etc. required power of 12V DC for operation
which can be drawn from the SAMEX system with
battery back up.
To program Zones on which sensors are connected
program as follows,
Password
+
and hang up.
Where
Z is Zone
for Z = 0 to 6 is Zone Number
for Z = * is all Zones
T is type of Sensor Norally Open(NO) or Closed(NC)
Where T is 0/1 for NO/NC respectively
To
disable a zone, which does not have sensors,
program as follows,
Password
+
and hang up.
For
example, on zone 1,2 and 3 Normally Open sensors
are connected and on zone 4 & 5 have NC sensors
but zone 6 is not used, then program as follows,
Password
+ (Enable
All for NO)
(Enable
Zone-4 for NC)
(Enable
Zone-5 for NC)
(Disable
Zone-6)
and hang up.
The
Entry Delay and Exit Delay are fixed at Two
Minutes.
|
|